3-phase Line Reactor to reduce mains disturbances
- 2% 3-phase line reactor for 690 V network
- Reducing harmonics on the mains side
- Reducing commutation notches
- Limiting inrush current
- Reliable and economical solution for mitigating mains disturbances
Features and Benefits
Ensure reliability, performance and a long service life of electrical consumers
Typical Applications
Motor drives and various adjustable speed drive systems, such as:
Technical Specifications
Nominal operating voltage
3x 500 to 690 VAC
Rated operating voltage
3x 450 to 760 VAC
Design corresponding to
UL 61800-5-1, EN 61558-2-20, EN 60076-6
Lifetime (calculated)
20 years
Earthing System
TN, TT, IT
Climatic category
40/100/21 (IEC 60068-1)
Pollution degree
PD3
Overvoltage category
OV III (IEC 60664-1 / UL 61800-5-1)
Impedance
2% @ 690 V, 50 Hz and rated rms current
Insulation class
UL electrical insulation system SCH-200(N)
Protection category
IP 00
Cooling
Natural cooling AN
Overload capability
1.6x rated current for 1 minute, once per hour
Ambient temperature range
-40°C to +45°C fully operational
+45°C to +100°C derated operation*
Note: derating according NEC 310-15(C)
Transportation and storage temperature
-40°C to +100°C transport and storage
Flammability corresponding to
UL 94V-0
*Iderated = Inominal*SQRT((Tmax-Tamb)/(Tmax-Tnominal)) = Inominal*SQRT((100°C-Tamb)/55°C)
*Iderated = Inominal*SQRT((Tmax-Tamb)/(Tmax-Tnominal)) = Inominal*SQRT((100°C-Tamb)/55°C)